Skip to main content

Protect your investment - schedule maintenance today

Seasonal
14 min read
July 5, 2026
Homeowner Guide

How to Winterize Your Sprinkler System in North Texas (You Don't Need a Blowout)

North Texas gets two different winter events, and they need two different protocols. One takes fifteen minutes on a single above-ground part. The other is the rare case where draining the system down actually pays. The forecast tells you which one you are in.

BS

Brandon Surratt

TCEQ Licensed Irrigator

Irrigation technician inspecting an above-ground backflow assembly before a North Texas freeze

North Texas gets two completely different winter events, and the entire argument about sprinkler winterization comes from people answering about one of them while you are asking about the other.

The event that recurs here is a cold day. On January 15, 2024, the high at DFW was 26 degrees, the lowest maximum temperature ever recorded at the airport for that date, beating 31 degrees from 1917, with a forecast low of 11. One day. That event needs about fifteen minutes of work on one above-ground part, and no blowout.

The other event is February 2021, when DFW hit a record low of minus 2 and stayed below freezing for 139 consecutive hours. That is a different physical problem, and it is the one case where draining the system down, or blowing it out, earns its money.

So the honest answer is not "you need a blowout" and it is not "winterization is a scam." It is: there are two protocols, and the thing that tells you which one you are in is the forecast, not the calendar.

What you'll learn:

  • The two freeze events DFW actually gets, with the real numbers for each
  • The 15-minute protect-the-backflow routine for a normal cold day
  • When a full drain-down is genuinely worth it, and what triggers that call
  • Why buried pipe under six inches of backfill does not freeze on a single cold night
  • The self-inflicted failure in the manufacturer's own manual that nobody mentions
  • How to spot freeze damage when the weather warms up, and how to start up in spring

Time needed: 15 minutes for the normal event Difficulty: Beginner-friendly (most of this is a shut-off valve, two test cocks, and a cover)

KEY TAKEAWAYS
  • Two events, two protocols: a 26-degree day (Jan 2024) and 139 hours below freezing (Feb 2021)
  • The trigger is forecast sustained sub-freezing hours, not a date on the calendar
  • For the normal event: close the supply, relieve the assembly, insulate it, controller off. Fifteen minutes
  • Buried pipe survives on soil thermal mass, not on a "frost line." DFW has no meaningful design frost depth
  • Closing the isolation valve and walking away from a charged line is its own failure mode, per the manufacturer

Why North Texas Is Different From Blowout Country

Residential sprinkler system running in front of a modern North Texas home in cool weather
On a normal DFW cold day a system doesn't need its lines emptied. The soil around buried pipe holds enough heat to carry it through a single night.
  • Jan 15, 2024: high of 26°F, one day
  • Feb 2021: low of −2°F, 139 hours below freezing
  • Normal event: protect the assembly, 15 minutes
  • Uri event: drain it down or blow it out

The whole point of a compressed-air blowout is to get water out of buried pipe before the ground freezes deep enough to reach it. In the northern states, frost drives several feet down and stays there for the winter. If there's water in a lateral line at that depth, it freezes, expands, and cracks the pipe. So they empty the entire system.

North Texas frost doesn't behave that way. Our freezes come in short bursts, usually a cold night or two, then a thaw.

Why buried pipe survives a cold night

This part gets explained badly everywhere, including by companies that reach the right conclusion. Texas irrigation rule 30 TAC 344.62(l) requires six inches of select backfill over buried pipe, and allows two inches only where a utility, a structure, or tree roots make six impractical. Six inches is not a frost depth, and there is no code anywhere requiring a Texas irrigation line to be buried below some frost line, because DFW has no meaningful design frost depth to begin with.

What actually keeps the water in that pipe liquid on a 26-degree day is the thermal mass of the soil around it. The ground holds heat and gives it up slowly. A single cold night, even a cold day and night, does not pull enough heat out of the top six inches of soil to drive a freeze front down to the pipe and then keep it there long enough to turn the water inside to ice.

Two versions of this get written up wrong, and they lead to opposite mistakes:

  • "A short dip to 31 for two hours is fine, but 28 degrees for six hours will freeze your buried lines." It won't, not under six inches of backfill in this soil. On a single-night event what freezes is the above-ground assembly and anything else exposed. That framing overstates the risk to the buried system.
  • "Texas pipe is buried below the frost line, roughly eight to twelve inches." Right conclusion, invented mechanism. The rule says six inches, for installation reasons, and the protection comes from soil thermal mass rather than from clearing a frost line that doesn't exist here.

The reason the mechanism matters: if the protection were a frost line, the answer would never change. Because the protection is thermal mass, it has a limit, and sustained cold is what exhausts it. That is exactly what separates January 2024 from February 2021.

So the expensive part of northern winterization, evacuating every buried line, solves a problem you don't have in a normal DFW winter. For the event we get most years, most homeowners can handle winter prep themselves with a cover and five minutes of knowing where their valves are. We'd rather tell you that than sell you a service you don't need.

The trigger isn't a date on the calendar. It's how many hours the forecast says we stay below freezing.

Brandon Surratt, Licensed Irrigator

The Two Freezes North Texas Gets

Here are both events with their real numbers, and the protocol each one calls for.

The normal event: a cold day

January 15, 2024. The high at DFW was 26 degrees, the lowest maximum temperature ever recorded there for that date, breaking a 31-degree record from 1917, with a forecast low of 11. It was a cold day inside a week that warmed back up. This is the freeze profile North Texas actually gets, and it recurs.

What it threatens: the above-ground backflow assembly, the exposed risers under it, the ball valves, and any other above-grade pipe. Not your buried laterals.

Protocol: controller off, close the irrigation isolation valve, relieve the assembly at the test cocks, insulate the assembly including the risers all the way to the ground. Fifteen minutes, no compressor, no service call. That routine is the next section.

The Uri event: sustained cold

February 2021. DFW recorded a low of minus 2 degrees, the second-coldest temperature ever recorded at the airport (the record is minus 8, set February 12, 1899), and the coldest in North Texas since January 1949. Temperatures stayed below freezing for 139 consecutive hours.

That is not the same problem with a bigger number on it. Nearly six straight days with no daytime thaw is long enough to work the cold down through the soil, and there is no warm afternoon in the middle to bail out a part you missed. This is the one case in DFW where draining the system down, or a proper compressed-air blowout, earns what it costs.

The trigger

Not a calendar date. The useful question before a cold snap is: how many consecutive hours does the forecast keep us below freezing, and how far below?

  • A night or a day below freezing, back above 32 the next afternoon: the 15-minute routine. Protect the above-ground assembly and leave the buried system alone.
  • Multiple days with no thaw, lows in the teens or lower: go further. Drain down what will drain, consider a blowout, and treat shallow or exposed pipe as at risk. This is also the case where an empty, unheated property deserves the full treatment.

A date-based rule ("blow it out every October") gets both of those wrong. It charges you for the big protocol in the years you needed the small one, and it has already been performed and forgotten by the time a February event shows up.

That said, "you don't need a blowout" is not the same as "do nothing." The thing that fails in a normal North Texas freeze isn't buried, it's sitting right out in the open. Let's talk about what that is.

What Actually Freezes Here (Backflow First)

Technician inspecting an above-ground irrigation valve and backflow assembly
The backflow preventer sits above ground with water trapped inside. That's why it's the first thing to crack in a hard freeze.

If freeze damage hits your system, it almost always starts in the same place: the backflow preventer, sometimes called the vacuum breaker or the anti-siphon assembly. This is the brass or plastic device that sits above ground, usually near where your water line meets the irrigation system, often along the side of the house or near the meter.

Here's why it's so vulnerable. Everything else in your system is either buried or drains out. The backflow preventer sits up in the open air with water trapped inside its body. When a hard freeze hits, that trapped water freezes, expands, and cracks the housing or blows out an internal seal. Come spring, you turn the system on and get a fountain shooting straight up out of the assembly.

After the backflow, the next things at risk are anything else exposed:

  • Above-ground pipe. Any PVC or poly riser that runs up a wall or across an exposed area holds water that can freeze.
  • The shut-off and supply valves near the surface. If a valve body sits shallow or in an uninsulated box, a severe freeze can reach it.
  • Shallow heads and lines near the surface. Most lines are safely deep, but a head that was installed too shallow, or a line that heaved close to the surface over the years, can freeze in a bad cold snap.
PRO TIP

Walk your yard now and find your backflow preventer. It's the above-ground brass or plastic assembly, usually knee-high, near the water meter or the side of the house. That one part is what winter prep is really about.

Notice what's not on that list: your buried lateral lines, the ones a northern blowout is designed to protect. On a 26-degree day under six inches of backfill they're fine. The 139 consecutive hours below freezing in February 2021 is the scenario that pushes risk down to them, and even in that event the above-ground assembly is what fails first and most often. Protect the exposed parts and you've handled the vast majority of freeze risk in DFW.

The order of casualties, worst first, is worth knowing because it tells you where to spend your fifteen minutes: above-grade backflow assembly, then valves sitting in boxes, then lateral lines, then your controller programming. The assembly sits in open air with water trapped in it, so it freezes first, and it is one of the pricier single parts on the system to replace.

A second casualty people miss: the valve boxes themselves. A lid that is cracked or not fully seated lets water stand in the box, and water standing in a box that freezes can crack the valve body underneath it. Walking the boxes is part of the same trip.

The 15-Minute Protect-the-Backflow Routine

Smart irrigation controller mounted in a clean garage, ready to be switched off for winter
Switching the controller to off or rain mode keeps the system from running during a freeze, when watering does more harm than good.

This is the protocol for the normal event: one cold day or night, back above freezing the next afternoon. It is fifteen minutes of work on the parts that sit in open air, and it is the whole job for the freeze DFW gets most years. Step 1 is a one-time errand you do on a calm afternoon, well before any of this.

1. Locate your shut-off valve before you need it.

This is the single most important step, and it costs nothing. Find the valve that shuts off water to your irrigation system. It's usually near the water meter, in a valve box near the backflow, or where the irrigation line branches off your main supply. Some homes have it inside a garage or utility area. Turn it a quarter turn to confirm it moves, then leave it in whatever position you need. Doing this on a calm afternoon beats hunting for it in the dark during a freeze warning with water already spraying. Our emergency shut-off guide walks through finding it if you're not sure which valve it is.

2. Shut off the irrigation water supply.

Any time the forecast puts us below freezing for more than a brief dip, close that shut-off valve. This stops water from feeding the backflow and exposed pipe, and it means that if something does crack, you're not dumping water all night. It also closes off the sneaky version of this failure: a zone valve weeping a little can keep an above-grade riser full all night, and a full riser splits.

3. Relieve and drain the backflow preventer. Do not skip this one.

With the supply shut off, relieve the water trapped in the backflow. Most assemblies have two small test cocks (little valves with a slotted screw or small handle) and bleed valves. Open them a quarter to half turn to let the trapped water drain out and to give any remaining water room to expand without cracking the body. Leave them slightly open through the freeze. This one step prevents the most common freeze failure we see.

While the valves are in your hand: leaving each ball valve at roughly 45 degrees, halfway between open and closed, keeps a pocket of water from sitting trapped inside the ball itself. A ball valve that freezes with water inside it splits, and on a commercial 2-inch brass valve that is not a cheap part. Watts publishes that half-open position in its own winterization instructions for the Febco 765 so the valve bodies drain.

Closing the valve without relieving it is its own failure

Febco's installation manual for the 765, the most common pressure vacuum breaker on DFW homes, carries a warning that appears in no competitor article: thermal water expansion and water hammer downstream of the assembly "can cause excessive pressure increases," and those conditions must be eliminated to avoid damage. Here is what that looks like on a Saturday. You close the isolation valve, you leave the assembly and the line behind it full of water, the afternoon sun comes out, and the water in that sealed section warms and expands with nowhere to go. That is a pressure failure, not a freeze failure, and it cracks assemblies in weather that never got cold. Closing the valve is step one. Relieving the pressure at the test cocks is what makes step one safe. Never close an isolation valve on a charged line and walk away.

4. Insulate the backflow and any exposed pipe.

Wrap the backflow assembly. You can buy an insulated backflow cover, or improvise with foam pipe insulation plus an old towel tucked into a plastic bag to keep it dry. Cover any above-ground pipe the same way with foam pipe sleeves. The goal is simple: keep the exposed metal and plastic from reaching freezing temperature. A cheap foam cover here protects a part that costs real money to replace.

5. Set the controller to off or rain mode.

Switch your controller off, or into rain or seasonal-off mode, for the stretch of cold. You don't want the system running and spraying water in freezing weather, which glazes sidewalks and driveways with ice and does the lawn no good while it's dormant. A smart controller often handles this automatically with a freeze skip, but confirm it. If you want to walk through your controller's seasonal settings, our controller programming notes cover the common models.

  • Find the shut-off valve (do this ahead of time)
  • Close the irrigation supply
  • Relieve the assembly at the test cocks, valves at 45°
  • Insulate the assembly and the risers to the ground
  • Switch the controller to off or rain mode

That's it. No compressor, no service call, no emptying the buried lines. For most homes in Garland, Richardson, Frisco, and across the Metroplex, on the freeze we get most years, that checklist is the entire job. The backflow freeze protection guide goes deeper on the assembly itself: which types freeze, what to wrap it with, and what the risers do and don't drain.

One more thing worth doing the day before, and it has nothing to do with the hardware: if the soil is dry, water once. Moist soil holds heat better than dry soil, which protects roots through a freeze. Do it a day or two ahead, by hand or hose-end once the system is shut down, not with the system running into the cold. Our seasonal watering schedule covers the dormant-season side of that, and the clay soil guide explains why a single long pass on this soil mostly runs off instead of soaking in.

How to Drain a Sprinkler System (and When You Actually Need To)

If you came here searching how to drain your sprinkler system, here's the North Texas answer up front: for most DFW homes, "draining" means draining the backflow preventer, which is step 3 above. You do not need to empty every buried line the way a homeowner in Denver or Minneapolis does. But some systems have drain points worth knowing about, and there are a few cases where a fuller drain-down is worth the effort.

Draining the backflow is the drain that matters here. The trapped water sitting in the above-ground backflow is the water that freezes and cracks the housing. Shut off the supply, open the two test cocks and the bleed valves, and let it empty. For the large majority of DFW systems, that is the entire drain.

Check whether your system has drain valves. Some systems were built with manual drain valves or automatic drain valves at the low points of each zone. A manual drain valve is a small valve you open by hand to let a zone's water run out. An automatic drain valve opens on its own once the line loses pressure. If your installer put them in, you'll usually find them in valve boxes at the lowest point of a zone. Most North Texas systems don't have them and don't need them, but if yours does, opening the manual ones after you shut off the supply lets the lateral lines drain down.

When a fuller drain-down is worth it in DFW. Four situations justify going past the backflow: above-ground or shallow pipe that can't be avoided, raised-bed drip or exposed heads, a property sitting empty and unheated through winter, and a forecast like February 2021, where the cold holds for days instead of hours. That last one is the trigger that matters, and it is a forecast call, not an October appointment.

If you are reaching for a compressor, two cautions. A typical homeowner compressor does not move enough air volume to clear a zone properly, and cranking the pressure up to compensate is how heads and fittings get destroyed. Too much air, or air held in one zone too long, also damages valve diaphragms. This is the one piece of winterization where the DIY version can cost more than the freeze would have. If you're genuinely unsure whether your system needs more than backflow draining, that's a good reason to have someone look at it once before the first freeze rather than guess. That's exactly what the winter visit in our seasonal maintenance service covers: we shut off at your backflow assembly, gravity drain it, insulate what sits exposed, and shut the controller down. No compressor involved.

What to Do During a Multi-Day Hard Freeze

Water geysering from an irrigation line, the kind of failure a cracked backflow can cause
When a backflow cracks in a freeze, this is what spring start-up looks like. Shutting off the supply first keeps a crack from becoming a flood.

Most North Texas winters never push past a cold day. But every few years we get the real thing. February 2021 is the reference point and the numbers are worth keeping in mind, because they are what "hard freeze" means at the far end: a record low of minus 2 degrees, second-coldest ever recorded at DFW behind minus 8 in February 1899, and 139 consecutive hours below freezing. Nearly six days with no thaw.

The thing that makes a sustained event different is not the number on the thermometer, it's the absence of a daytime recovery. Soil thermal mass is a buffer, and a buffer with no chance to recharge eventually runs out.

When the forecast shows multiple days below freezing:

  • Keep the irrigation supply shut off for the full duration, not just overnight. When it stays below freezing around the clock, there's no daytime thaw to bail you out.
  • Leave the backflow drained and covered. Confirm the test cocks and bleeds are still cracked open and the insulation is dry and in place. Wet insulation doesn't insulate.
  • Leave the controller off. No watering during the freeze. A dormant winter lawn does not need it, and running the system in these temperatures creates ice hazards and can freeze water right in the heads.
  • Don't drip your irrigation system to prevent freezing. That trick is for indoor household plumbing, not your sprinkler backflow. For irrigation, drained and dry beats a trickle of water sitting in the assembly.
  • Photograph your controller schedule first. Many controllers hold their program on a 9-volt battery through a power outage, and a multi-day winter storm is exactly when the outage and the dead battery find each other. A photo of each zone's run times takes a minute and saves reprogramming the whole system in spring.
  • This is the event where going past the backflow pays. Drain down what will drain, and treat shallow pipe, exposed risers, raised-bed drip, and above-grade heads as at risk rather than fine.

The homeowners who came through February 2021 without a cracked backflow were, almost without exception, the ones who had shut off the supply and relieved the assembly ahead of time. It's a fifteen-minute task that protects a part which is a headache to replace in the middle of winter.

Signs of Freeze Damage When It Warms Up

Water gushing from a cracked irrigation pipe after a freeze
A zone that won't hold pressure or a soggy spot over a line can mean a freeze cracked something underground.

Freeze damage often hides until the first time you run the system in spring. Water pressure finds the crack, and suddenly the problem is obvious. Here's what to watch for the first few times you turn things on after winter:

  • A cracked backflow body. Look for a visible split in the brass or plastic housing, or water weeping from a seam that wasn't wet before. This is the most common freeze failure by far.
  • A geyser at the backflow or vacuum breaker. Turn the system on and water shoots straight up out of the assembly. That's a blown seal or a cracked body from ice expansion.
  • A zone that won't hold pressure. A zone that used to run fine now has weak, sputtering heads, or heads that barely pop up. That can mean a line cracked underground where it sat too shallow.
  • A soggy spot or bubbling over a buried line. Water surfacing in the yard where it never did before points to a split line beneath it. Our underground leak guide shows how to confirm and locate it with the water meter test.
  • A valve that weeps constantly. A valve that seeps even when its zone is off may have a freeze-damaged seal or body.

If you spot any of these, shut the system off at the supply and don't keep running it. Running a cracked system just wastes water and can worsen the damage. A cracked backflow or a burst line is a straightforward sprinkler repair, and a damaged backflow assembly specifically is a backflow repair we handle routinely across DFW. Catching it early, before you're relying on the system in July heat, keeps a small repair from becoming a dead lawn.

Spring Start-Up Done Right

Pressure gauge being used to test an irrigation system during spring start-up
Re-pressurize slowly in spring. Slamming a cold system with full pressure is how you turn a hairline crack into a burst.

Bringing your system back to life in spring is as much about protecting it as waking it up. The biggest mistake is throwing the shut-off wide open and hitting a cold, empty system with full pressure all at once. That pressure surge, called water hammer, can burst a line or finish off a component that a freeze already weakened.

Do it slowly and deliberately:

Wait for the last hard freeze. In North Texas that's usually mid-March. Don't rush the system back online in February just because you get a warm week. Another freeze can still come.

Re-pressurize slowly. Before you open the supply, close the backflow test cocks and bleed valves you left open for winter. Then open the main shut-off valve slowly, maybe a quarter of the way, and let the system fill gradually. You'll hear water moving. Give it a minute or two to fully pressurize before opening the valve the rest of the way. This gentle fill is the single best thing you can do to avoid a start-up blowout.

Walk every zone, one at a time. Run each zone manually from the controller and watch it. Look for heads that won't pop up, heads spraying sideways or misting, dry patches, soggy spots, and any weeping at the backflow or valves. This is when winter damage reveals itself, so take your time and look closely.

Reset your controller schedule. Move the controller out of off or rain mode and back to a proper spring schedule. Early spring in DFW is mild and often rainy, so you likely need less water than peak summer. Our seasonal watering schedule has real runtime numbers for the transition.

For a full walkthrough with photos, our spring start-up guide covers each step in more depth. And if you'd rather have a set of trained eyes confirm nothing cracked over the winter, a start-up visit is a bookable service, more on that next.

When to Book a Pro

Most of this you can do yourself, and we mean that. Finding your shut-off, draining and wrapping the backflow, flipping the controller off: none of it requires a technician. The honesty is the whole point. But there are a few situations where it makes sense to hand it off.

You're not sure where your shut-off or backflow is. If you've walked the yard and still can't identify the shut-off valve or the backflow assembly, that's worth a visit before the first freeze rather than after. We'll locate everything, show you how it works, and prep it for winter. If you bought the house recently and inherited the system with it, bought a house with a sprinkler system and taking over the sprinkler system walk through what to find and write down first.

You want winterization handled and off your plate. A seasonal winterization visit means we shut off the supply, drain and insulate the backflow, set the controller correctly, and confirm nothing is exposed. If you travel over winter or just don't want to think about it, this is a straightforward service to book. Better Earth Solutions covers the DFW Metroplex, and we're a TCEQ Licensed Irrigator, license LI0023963, with a 4.9 star rating across 100-plus Google reviews.

Something cracked and you need it repaired. A cracked backflow body, a geyser at the vacuum breaker, a zone that won't hold pressure after winter: these are repairs, not DIY winterizing. We fix freeze-damaged backflow assemblies and burst lines throughout Allen, Plano, Frisco, Wylie, Garland, and Richardson.

You want a professional spring start-up. If you'd rather have someone re-pressurize the system slowly, walk every zone, and catch any winter damage before you're depending on the system in summer, a start-up visit does exactly that.

The funnel here is simple and honest: do the basics yourself, book us if you'd rather have it done, and call us if something breaks. Winter prep in North Texas is a small job. The only expensive mistake is skipping it entirely and finding a cracked backflow in April.

If you want a hand now, you can book online or reach us at (469) 209-4110. We also keep an interactive freeze-prep tool that walks you through the checklist step by step when a cold snap is on the way.

Frequently Asked Questions

Do I need to winterize my sprinkler system in Texas?

Yes, but there are two different jobs and you need to know which one the forecast is asking for. For the event DFW gets most years, a cold day that warms back up, it is fifteen minutes: controller off, close the irrigation isolation valve, relieve the above-ground backflow assembly at its test cocks, and insulate the assembly including the risers. No compressed-air blowout. For a sustained event like February 2021, when DFW sat below freezing for 139 consecutive hours, going further and draining the system down is justified.

At what temperature should I worry about my sprinkler system?

Watch hours below freezing, not the low temperature by itself. A night or a day below 32 that recovers the next afternoon calls for protecting the above-ground assembly and nothing more. January 15, 2024 was that event: a high of 26 at DFW, the lowest maximum ever recorded there for that date, and a forecast low of 11. February 2021 was the other kind, with a record low of minus 2 and 139 consecutive hours below freezing. The difference is whether the cold holds long enough that there is no daytime thaw to bail you out.

Why don't my buried sprinkler lines freeze?

Not because of a frost line. Texas rule 30 TAC 344.62(l) requires only six inches of select backfill over buried irrigation pipe, and DFW has no meaningful design frost depth. What protects the pipe is the thermal mass of the soil around it: the ground gives up heat slowly, and one cold night does not pull enough heat out of six inches of soil to freeze the water inside the pipe. That protection has a limit, which is why a multi-day freeze with no thaw is a different situation.

Should I blow out my sprinkler lines in Dallas-Fort Worth?

Not on an annual schedule, and not for a normal cold day. Blowouts are built for climates where frost drives feet down and stays for months. Here, a drained and insulated backflow assembly plus knowing your shut-off protects you at a fraction of the cost, and it targets the part that actually freezes. The exception is a forecast like February 2021: multiple days with no thaw, lows in the teens or lower, or a property that is empty and unheated. That is when a full drain-down or a blowout earns its money, and it is a forecast call rather than a calendar one.

Can I damage my backflow just by shutting the water off?

Yes, if you close the valve and walk away with the line still full. Febco's manual for the 765 pressure vacuum breaker warns that thermal water expansion and water hammer downstream of the assembly can cause excessive pressure increases, and that those conditions have to be eliminated. A sealed section of charged pipe warming up in the afternoon sun has nowhere to put that expansion. Close the isolation valve, then relieve the pressure at the test cocks. The two steps go together.

How do I drain a sprinkler system in Texas?

For most DFW systems, draining means draining the above-ground backflow preventer, not emptying the buried lines. Shut off the irrigation supply, open the two test cocks and the bleed valves on the backflow, and let the trapped water run out. Some systems also have manual or automatic drain valves at the low points of each zone. If yours does, opening the manual ones after the supply is off drains the lateral lines too. A full drain-down only makes sense for exposed or shallow pipe, an empty unheated property, or a rare severe multi-day freeze.

How do I protect my backflow preventer from freezing?

The backflow preventer sits above ground and is the number one freeze casualty. Before a hard freeze, shut off the irrigation supply valve, then open the two test cocks and the bleed valves on the backflow to drain the water trapped inside. Wrap the assembly in an insulated cover or foam pipe insulation and a towel inside a plastic bag. Drained plus insulated is what keeps it from cracking.

What are the signs my sprinkler system froze and cracked?

The most common one is a cracked backflow body or a geyser shooting up from the backflow or a vacuum breaker the first time the system runs in spring. Others include a zone that will not hold pressure, water bubbling up from the ground over a buried line, or a valve that weeps constantly. If you see any of these, shut the system off and have the damaged part repaired before running it further.

When should I turn my sprinklers back on in spring?

Wait until the last hard freeze has passed, usually mid-March in North Texas. Turn the water on slowly to re-pressurize the system gently instead of slamming it with full pressure, then walk every zone one at a time and watch for leaks, broken heads, and low pressure. Fixing a cracked backflow or a burst line before you rely on the system beats discovering it in July.


References

  1. National Weather Service via The Dallas Morning News, January 17, 2024. DFW high of 26°F on January 15, 2024, the lowest maximum on record for that date, beating 31°F in 1917.
  2. WFAA, "North Texas' most significant winter weather events in history." February 2021 record low of −2°F at DFW, second-coldest on record behind −8°F on February 12, 1899, and 139 consecutive hours below freezing.
  3. 30 Texas Administrative Code § 344.62(l). Six inches of select backfill over buried irrigation pipe, two inches where a utility, structure, or roots make six impractical.
  4. 30 Texas Administrative Code § 344.62(k). New systems require an isolation valve between the water meter and the backflow prevention assembly.
  5. Febco, Installation, Operation and Maintenance Instructions, Model 765 Pressure Vacuum Breaker (IOM-F-765). "The device must be protected from freezing." Thermal water expansion and downstream water hammer can cause excessive pressure increases.
  6. Watts, Winterization Instructions for Febco Model 765 (IS-F-765-Winterization). Keep the system shut-off closed for the winter; after draining, leave ball valves half open so the valve bodies drain.

This information is provided for educational purposes. Some irrigation repairs may require knowledge of local plumbing codes or specialized equipment. If you're unsure about any repair, contact a licensed irrigation professional in your area.

Better Earth Solutions serves the DFW Metroplex including Allen, Plano, Wylie, Garland, Richardson, Rowlett, Murphy, Dallas, Rockwall, Heath, and Lucas. For seasonal winterization, spring start-up, or freeze-damage repair, call (469) 209-4110 or book online.


Winter in North Texas usually calls for a cover, a relieved backflow, and knowing where your shut-off is before the freeze warning posts. Do those few things and your system rides out a cold day just fine. Watch the forecast for the other kind, the one that stays below freezing for days, and go further when it shows up.

One more thing the mild winters here make possible: the cool season is actually a workable time to put in a new system, since the ground never freezes to trenching depth and installation projects aren't competing with summer's repair rush. If your system is past saving rather than just cold, our best time to install guide covers the season-by-season tradeoffs.

Start with the one that costs nothing: go find your shut-off valve today, while the weather is calm and you're not standing in the dark. Everything else is easier once you know where it is.

Want the Winterization Done For You?

We serve 15 cities across the DFW Metroplex with expert irrigation repair, smart controller installation, and drainage solutions.

BS

Brandon Surratt

Better Earth Solutions

  • TCEQ Licensed Irrigator LI0023963
  • Texas Certified Landscape Irrigation Auditor (TxCLIA)
  • Rachio Expert

Last updated: